Error 2800
This error indicates that one or both of the auxiliary shutdown switches is in the off position. On the side of the generator the three light annunciator will show a red light. The controller will also be set to off and display the following message Stopped Alarm error code 2800. One switch is located on the back of the generator, and generators rated to 15kW and greater will have a second shutdown switch inside the generator housing on the firewall panel. These switches are intentionally made, easily accessible, and are to be used by fire department personnel in the event of an emergency. When off, these switches prevent the generator from running and in an emergency situation this can help prevent further complications. To reset and clear this alarm. First, locate the external switch on the back of the generator. Ensure the switch is on the eye or closed position. If applicable, locate the internal switch on the inside panel of the generator. Both of these switches must be on. Otherwise the generator will not run. After verifying and resetting the shut down switches, the controller will prompt the user to clear the alarm. Press the red off button, then the enter button. Next, press the green auto button to set the generator to automatic system operation. The generator is now ready to run in the event of a power outage. If this error code persists, a service visit from your local dealer may be required. #Generac #Generator #AirCooled